ARE4EX 0,6/1kV 3x150+95N
Certifications and labels
Environmental data
ARE4EX 0,6/1kV 3x150+95N
- Nexans ref. : 10581785
Description
Description
Standards
-
ProductHD 603; IEC 60502-1
Description
Helically bundled tetra polar cables with aluminium conductor, XLPE insulation, polyolefin outer sheath.
Cables compliant with the requirements of the Construction Products Regulation “CPR (EU) n° 305/2011”.
Fire performance class: Eca
Application:
Suitable for fixed installation laying indirectly buried.
Construction
- Conductor: stranded, compacted, round aluminium – Cl. 2 (CEI EN 60228).
- Insulation: extruded polyethylene (XLPE) compound.
- Outer sheath: extruded polyolefin (PO) compound. Colour: black.
Functional characteristics
- Rated voltages U0/U: 0,6/1 kV
- Max. operating temperature of conductor: 90°C
- Max. short circuit temperature of conductor: 250°C (max 5s)
- Min. installation temperature: -25°C
- Max. tensile strength on the conductor during installation: 50 N/mm2
- Min. bending radius during installation: 9 Dphase
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Dimensional characteristics
Dimensional characteristics
Electrical characteristics
Electrical characteristics
Resources
Resources
Declaration of Performance
- Declaration of Performance n° : 1001248-ITBP
- Certification Date : 7/3/25
- AVCP (Assessment and Verification of Constancy of Performance) : System 3
- Notified body : 0051
- Declared performance : Eca
ARE4EX 0,6/1kV 3x150+95N
Nexans ref. : 10581785
PEP : NXNS-00055-V04.01
This product is part of the low carbon range of Nexans : a selection of products ensuring the reduction of the carbon footprint and subject to rigourous ecodesign criteria.
Nexans Low Carbon Selection Criteria: minimum integration of 10% recycled copper or aluminum and/or 100% low-carbon aluminum sourcing.
Read more Read less- Amount of CO2 emitted Cradle to Gate phase (raw material collection and manufacturing), for the production of 1 km of cable.
- 7.3t CO2 / t represents the European average (International Aluminium Institute 2019).
- The product reference value is calculated based on the final average value of aluminium. The reductions achieved are linked to the use of carbon-free energy sources.