ARP1H5E(X) 12/20kV / Fca POWERBOOST™

Products

ARP1H5E 12/20kV 1x185 IT

Nexans ref. 10546369

  • Lay Up: Single core
  • Number of cores: 1
  • Number of phases: -
  • Conductor cross-section: 185 mm²
  • Phase Conductor Cross Section: - mm²
  • Conductor diameter: 16.0 mm
  • Phase Conductor Diameter: - mm
  • Diameter over insulation: 26.4 mm
  • Nominal outer sheath thickness: 2.75 mm
  • Nominal outer diameter: 35.5 mm
  • Nominal overall diameter of each phase cable: - mm
  • Nominal overall diameter: - mm
  • Approximate weight: 1190 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.164 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.211 Ohm/km
  • Perm. current rating buried 20°C - trefoil formation: 314 A
  • Permissible current rating in air 40°C - trefoil formation: 369 A
  • Permissible short circuit current conductor 1s: 17.5 kA
  • Permissible short circuit current screen 0.5s: 2.8 kA

 

ARP1H5E 12/20kV 1x240 IT

Nexans ref. 10557598

  • Lay Up: Single core
  • Number of cores: 1
  • Number of phases: -
  • Conductor cross-section: 240 mm²
  • Phase Conductor Cross Section: - mm²
  • Conductor diameter: 18.5 mm
  • Phase Conductor Diameter: - mm
  • Diameter over insulation: 28.9 mm
  • Nominal outer sheath thickness: 3.0 mm
  • Nominal outer diameter: 38.5 mm
  • Nominal overall diameter of each phase cable: - mm
  • Nominal overall diameter: - mm
  • Approximate weight: 1440 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.125 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.161 Ohm/km
  • Perm. current rating buried 20°C - trefoil formation: 364 A
  • Permissible current rating in air 40°C - trefoil formation: 438 A
  • Permissible short circuit current conductor 1s: 22.7 kA
  • Permissible short circuit current screen 0.5s: 3 kA

 

ARP1H5EX 12/20kV 3x1x185 IT

Nexans ref. 10546371

  • Lay Up: Twisted single cores
  • Number of cores: 3
  • Number of phases: 3
  • Conductor cross-section: - mm²
  • Phase Conductor Cross Section: 185 mm²
  • Conductor diameter: - mm
  • Phase Conductor Diameter: 16 mm
  • Diameter over insulation: 26.4 mm
  • Nominal outer sheath thickness: 2.75 mm
  • Nominal outer diameter: - mm
  • Nominal overall diameter of each phase cable: 35.5 mm
  • Nominal overall diameter: 76.4 mm
  • Approximate weight: 3560 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.164 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.211 Ohm/km
  • Perm. current rating buried 20°C - trefoil formation: 314 A
  • Permissible current rating in air 40°C - trefoil formation: 369 A
  • Permissible short circuit current conductor 1s: 17.5 kA
  • Permissible short circuit current screen 0.5s: 2.8 kA

 

ARP1H5EX 12/20kV 3x1x240 IT

Nexans ref. 10546277

  • Lay Up: Twisted single cores
  • Number of cores: 3
  • Number of phases: 3
  • Conductor cross-section: - mm²
  • Phase Conductor Cross Section: 240 mm²
  • Conductor diameter: - mm
  • Phase Conductor Diameter: 18.5 mm
  • Diameter over insulation: 28.9 mm
  • Nominal outer sheath thickness: 3.0 mm
  • Nominal outer diameter: - mm
  • Nominal overall diameter of each phase cable: 38.5 mm
  • Nominal overall diameter: 83.1 mm
  • Approximate weight: 4320 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.125 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.161 Ohm/km
  • Perm. current rating buried 20°C - trefoil formation: 364 A
  • Permissible current rating in air 40°C - trefoil formation: 438 A
  • Permissible short circuit current conductor 1s: 22.7 kA
  • Permissible short circuit current screen 0.5s: 3 kA

 

ARP1H5EX 12/20kV 3x1x95 IT

Nexans ref. 10548226

  • Lay Up: Twisted single cores
  • Number of cores: 3
  • Number of phases: 3
  • Conductor cross-section: - mm²
  • Phase Conductor Cross Section: 95 mm²
  • Conductor diameter: - mm
  • Phase Conductor Diameter: 11.5 mm
  • Diameter over insulation: 21.9 mm
  • Nominal outer sheath thickness: 2.75 mm
  • Nominal outer diameter: - mm
  • Nominal overall diameter of each phase cable: 30.8 mm
  • Nominal overall diameter: 66.3 mm
  • Approximate weight: 2520 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.32 Ohm/km
  • A.C. Conductor resist. 50Hz and at 90 °C: 0.411 Ohm/km
  • Perm. current rating buried 20°C - trefoil formation: 218 A
  • Permissible current rating in air 40°C - trefoil formation: 245 A
  • Permissible short circuit current conductor 1s: 9 kA
  • Permissible short circuit current screen 0.5s: 2.4 kA

 

Description

Description

Standards

  • National
    GSC001

Single core and helically bundled tripolar cables with aluminium conductor, HPTE insulation, aluminium tape screen, PE outer sheath.

Cables compliant with the requirements of the Construction Products Regulation “CPR (EU) n° 305/2011”.

Fire performance class: Fca

Application:

Suitable for fixed installation laying indirectly buried.

Construction:

  • Conductor: stranded, compacted, round aluminium – Cl. 2  (IEC 60228).
  • Conductor screen: extruded semiconducting compound.
  • Insulation: extruded high performance polypropylene thermoplastic elastomer (HPTE) compound.
  • Insulation screen: extruded semiconducting compound – easy strippable.
  • Longitudinal watertightness: semiconducting water blocking tape.
  • Screen and radial watertightness: aluminium tape longitudinally applied (nominal thickness: 0,3 mm).
  • Outer sheath: extruded polyethylene (PE) compound. Colour: red.

Functional characteristics:

  • Rated voltages U0/U: 12/20 kV
  • Max. operating temperature of conductor: 90°C
  • Max. short circuit temperature of conductor: 250°C (max 5s)
  • Max. short circuit temperature of screen: 150°C
  • Min. installation temperature: -25°C
  • Max. tensile strength on the conductor during installation: 50 N/mm2
  • Min. bending radius during installation (single core cables): 14 Dcable
  • Min. bending radius during installation (tripolar cables): 21 Dphase

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Aluminum
Conductor shape
Round, stranded and compacted
Conductor flexibility
Class 2 acc. to IEC 60228
Material of the inner semi-conductor
Extruded semiconducting compound
Insulation
Extruded HPTE compound
Material of the external semi-conductor
Extruded semiconducting compound - easy strippable
Material used for longitudinal water tightness
Semiconducting swellable tape
Screen
Aluminium tape
Outer sheath
Extruded PE compound
Sheath colour
Red

Dimensional characteristics

Dimensional characteristics

Nominal insulation thickness
4.9 mm
Minimum insulation thickness
4.31 mm
Screen thickness
300 µm

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
12 / 20 (24) kV
Thermal soil resistivity dry zone
1.5 °K.m/W
Grounding type
Solid bonding

Usage characteristics

Usage characteristics

Laying depth, center of system
800 mm

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close