- Markets
- Products
- Newsroom
- About Nexans
- Tools & Resources
- Search
- Contact us
- Compare
- Sign in
ARE4H5E 18/30kV SR/0,2 / Eca
ARE4H5E 18/30kV 1x185 SR/0,2
Nexans ref. 10582008
- Conductor cross-section: 185 mm²
- Conductor diameter: 16.0 mm
- Minimum insulation thickness: 6.0 mm
- Diameter over insulation: 29.8 mm
- Nominal outer sheath thickness: 2.1 mm
- Nominal outer diameter: 37.6 mm
- Approximate weight: 1280 kg/km
- Max. DC resistance of the conductor at 20°C: 0.164 Ohm/km
- A.C. Conductor resist. 50Hz and at 90 °C: 0.211 Ohm/km
- Perm. current rating buried 20°C - trefoil formation: 319 A
- Perm. current rating in air 30°C - trefoil formation: 426 A
- Permissible short circuit current conductor 1s: 17.5 kA
- Permissible short circuit current screen 0.5s: 2.1 kA
ARE4H5E 18/30kV 1x400 SR/0,2
Nexans ref. 10582007
- Conductor cross-section: 400 mm²
- Conductor diameter: 23.5 mm
- Minimum insulation thickness: 6.0 mm
- Diameter over insulation: 37.3 mm
- Nominal outer sheath thickness: 2.4 mm
- Nominal outer diameter: 46.0 mm
- Approximate weight: 2070 kg/km
- Max. DC resistance of the conductor at 20°C: 0.0778 Ohm/km
- A.C. Conductor resist. 50Hz and at 90 °C: 0.101 Ohm/km
- Perm. current rating buried 20°C - trefoil formation: 477 A
- Perm. current rating in air 30°C - trefoil formation: 678 A
- Permissible short circuit current conductor 1s: 37.8 kA
- Permissible short circuit current screen 0.5s: 2.5 kA
ARE4H5E 18/30kV 1x500 SR/0,2
Nexans ref. 10578824
- Conductor cross-section: 500 mm²
- Conductor diameter: 26.5 mm
- Minimum insulation thickness: 6.1 mm
- Diameter over insulation: 40.8 mm
- Nominal outer sheath thickness: 2.5 mm
- Nominal outer diameter: 49.8 mm
- Approximate weight: 2500 kg/km
- Max. DC resistance of the conductor at 20°C: 0.0605 Ohm/km
- A.C. Conductor resist. 50Hz and at 90 °C: 0.08 Ohm/km
- Perm. current rating buried 20°C - trefoil formation: 545 A
- Perm. current rating in air 30°C - trefoil formation: 790 A
- Permissible short circuit current conductor 1s: 47.2 kA
- Permissible short circuit current screen 0.5s: 2.7 kA
ARE4H5E 18/30kV 1x630 SR/0,2
Nexans ref. 10576183
- Conductor cross-section: 630 mm²
- Conductor diameter: 30.0 mm
- Minimum insulation thickness: 6.2 mm
- Diameter over insulation: 44.5 mm
- Nominal outer sheath thickness: 2.6 mm
- Nominal outer diameter: 53.9 mm
- Approximate weight: 3030 kg/km
- Max. DC resistance of the conductor at 20°C: 0.0469 Ohm/km
- A.C. Conductor resist. 50Hz and at 90 °C: 0.063 Ohm/km
- Perm. current rating buried 20°C - trefoil formation: 620 A
- Perm. current rating in air 30°C - trefoil formation: 920 A
- Permissible short circuit current conductor 1s: 59.5 kA
- Permissible short circuit current screen 0.5s: 2.9 kA
Description
Description
Standards
- 
                                            ProductHD 620; IEC 60502-2
Description
Single core cables with aluminium conductor, reduced thickness XLPE insulation, aluminium tape screen, PE outer sheath.
Cables compliant with the requirements of the Construction Products Regulation “CPR (EU) n° 305/2011”.
Fire performance class: Eca
Application:
Suitable for fixed installation indoor or outdoor, laying in air or directly or indirectly buried.
Construction
- Conductor: stranded, compacted, round aluminium – Cl. 2 (IEC 60228).
- Conductor screen: extruded semiconducting compound.
- Insulation: extruded polyethylene (XLPE) compound.
- Insulation screen: extruded semiconducting compound – fully bonded.
- Longitudinal watertightness: semiconducting water blocking tape.
- Screen and radial watertightness: aluminium tape longitudinally applied (nominal thickness: 0,2 mm).
- Outer sheath: extruded polyethylene (PE) compound. Colour: red.
Functional characteristics
- Rated voltages U0/U: 18/30 kV
- Max. operating temperature of conductor: 90°C
- Max. short circuit temperature of conductor: 250°C (max 5s)
- Max. short circuit temperature of screen: 150°C
- Min. installation temperature: -25°C
- Max. tensile strength on the conductor during installation: 50 N/mm2
- Min. bending radius during installation: 14 Dcable
Characteristics
Characteristics
Construction characteristics
Construction characteristics
                                                            Conductor material
                                                        
                                                        
                                                            Aluminum 
                                                        
                                                    
                                                            Conductor shape
                                                        
                                                        
                                                            Round, stranded and compacted 
                                                        
                                                    
                                                            Conductor flexibility
                                                        
                                                        
                                                            Class 2 acc. to IEC 60228 
                                                        
                                                    
                                                            Material of the inner semi-conductor
                                                        
                                                        
                                                            Extruded semiconducting compound 
                                                        
                                                    
                                                            Insulation
                                                        
                                                        
                                                            Extruded XLPE compound 
                                                        
                                                    
                                                            Material of the external semi-conductor
                                                        
                                                        
                                                            Extruded semiconducting compound - fully bonded 
                                                        
                                                    
                                                            Material used for longitudinal water tightness
                                                        
                                                        
                                                            Semiconducting swellable tape 
                                                        
                                                    
                                                            Screen
                                                        
                                                        
                                                            Aluminium tape 
                                                        
                                                    
                                                            Outer sheath
                                                        
                                                        
                                                            Extruded PE compound 
                                                        
                                                    
                                                            Sheath colour
                                                        
                                                        
                                                            Red 
                                                        
                                                    Dimensional characteristics
Dimensional characteristics
                                                            Number of cores
                                                        
                                                        
                                                            1 
                                                        
                                                    
                                                            Screen thickness
                                                        
                                                        
                                                            200 µm
                                                        
                                                    Electrical characteristics
Electrical characteristics
                                                            Rated Voltage Uo/U (Um)
                                                        
                                                        
                                                            18 / 30 (36) kV 
                                                        
                                                    
                                                            Thermal soil resistivity dry zone
                                                        
                                                        
                                                            1.5 °K.m/W
                                                        
                                                    
                                                            Grounding type
                                                        
                                                        
                                                            Solid bonding 
                                                        
                                                    Usage characteristics
Usage characteristics
                                                            Laying depth, center of system
                                                        
                                                        