ARP1EX 0,6/1kV 3x150+95N IT
ARP1EX 0,6/1kV 3x150+95N IT
- Nexans ref. : 10577352
Description
Description
Standards
- 
                                            NationalGSC002
Description
Helically bundled tetra polar cables with aluminium conductor, HPTE insulation, polyolefin outer sheath.
Cables compliant with the requirements of the Construction Products Regulation “CPR (EU) n° 305/2011”.
Fire performance class: Eca
Application:
Suitable for fixed installation laying indirectly buried.
Construction
- Conductor: stranded, compacted, round aluminium – Cl. 2 (CEI EN 60228).
- Insulation: extruded high performance polypropylene thermoplastic elastomer (HPTE) compound.
- Outer sheath: extruded polyolefin (PO) compound. Colour: black.
Functional characteristics
- Rated voltages U0/U: 0,6/1 kV
- Max. operating temperature of conductor: 90°C
- Max. short circuit temperature of conductor: 250°C (max 5s)
- Min. installation temperature: -25°C
- Max. tensile strength on the conductor during installation: 50 N/mm2
- Min. bending radius during installation: 9 Dphase
Characteristics
Characteristics
Construction characteristics
Construction characteristics
                                                                Conductor material
                                                            
                                                            
                                                                Aluminum 
                                                            
                                                        
                                                                Conductor shape
                                                            
                                                            
                                                                Round, stranded and compacted 
                                                            
                                                        
                                                                Conductor flexibility
                                                            
                                                            
                                                                Class 2 acc. to IEC 60228 
                                                            
                                                        
                                                                With smaller neutral conductor
                                                            
                                                            
                                                                Yes 
                                                            
                                                        
                                                                Neutral Type
                                                            
                                                            
                                                                Aluminium - Class 2 acc. to IEC 60228 
                                                            
                                                        
                                                                Insulation
                                                            
                                                            
                                                                Extruded HPTE compound 
                                                            
                                                        
                                                                Insulation colour
                                                            
                                                            
                                                                Natural 
                                                            
                                                        
                                                                Lay Up
                                                            
                                                            
                                                                Twisted single cores 
                                                            
                                                        
                                                                Outer sheath
                                                            
                                                            
                                                                Extruded polyolefin-based thermoplastic compound 
                                                            
                                                        
                                                                Sheath colour
                                                            
                                                            
                                                                Black 
                                                            
                                                        Dimensional characteristics
Dimensional characteristics
                                                                Number of cores
                                                            
                                                            
                                                                4 
                                                            
                                                        
                                                                Number of phases
                                                            
                                                            
                                                                3 
                                                            
                                                        
                                                                Phase Conductor Cross Section
                                                            
                                                            
                                                                150 mm²
                                                            
                                                        
                                                                Neutral conductor section (when smaller)
                                                            
                                                            
                                                                95 mm²
                                                            
                                                        
                                                                Phase Conductor Diameter
                                                            
                                                            
                                                                14.3 mm
                                                            
                                                        
                                                                Neutral Conductor Diameter
                                                            
                                                            
                                                                11.5 mm
                                                            
                                                        
                                                                Average insulation thickness
                                                            
                                                            
                                                                1.4 mm
                                                            
                                                        
                                                                Insulation thickness of neutral conductor
                                                            
                                                            
                                                                1.10 mm
                                                            
                                                        
                                                                Average sheath thickness
                                                            
                                                            
                                                                1.4 mm
                                                            
                                                        
                                                                Sheath thickness of the neutral conductor
                                                            
                                                            
                                                                1.40 mm
                                                            
                                                        
                                                                Nominal overall diameter of each phase cable
                                                            
                                                            
                                                                21.6 mm
                                                            
                                                        
                                                                Nominal overall diameter
                                                            
                                                            
                                                                50.0 mm
                                                            
                                                        
                                                                Approximate weight
                                                            
                                                            
                                                                2040 kg/km
                                                            
                                                        Electrical characteristics
Electrical characteristics
                                                                Rated Voltage Uo/U (Um)
                                                            
                                                            
                                                                0.6/ 1 (1.2) kV 
                                                            
                                                        Resources
Resources
Declaration of Performance
- Declaration of Performance n� : 1001247-ITBP
- Certification Date : 7/3/25
- AVCP (Assessment and Verification of Constancy of Performance) : System 3
- Notified body : 0051
- Declared performance : Eca