Nexans PV AC/DC 1x240

Description

Description

Standards

  • Product
    EN 50575; EN 60529; IEC 60228; IEC 60502-1
  • Test
    HD 605

Applications

The PV AC/DC cable is designed for energy installations requiring performance and reliability:

  • Photovoltaic installations (solar plants, rooftops, infrastructures)
  • Installation in open air, on cable trays or indirectly buried
  • Outdoor environments and humid areas (AD7)
  • 1.8/3 kV according to IEC 60502-1 dielectric test, based on IMQ test report No. CN26-0132320-01

Construction and functional characteristics

  • Conductor: stranded, compacted, round aluminum – Cl. 2 (IEC 60228).
  • Insulation: extruded polyethylene (XLPE) compound. Colour: natural.
  • Outer sheath: extruded PVC compound. Colour: black. 
  • Max. operating temperature of conductor: 90°C
  • Max. short circuit temperature of conductor: 250°C (max 5s)
  • Min. installation temperature: 0°C
  • Max. tensile strength on the conductor during installation: 50 N/mm2
  • Min. bending radius during installation: 12 Dcable

Key advantages

  • XLPE insulation: excellent thermal resistance up to 90 °C in operation
  • High short-circuit resistance (up to 250 °C)
  • UV-resistant PVC sheath for outdoor applications
  • Suitable for humid environments (AD7) acc. to IEC 60364-5-51
  • Compliant with IEC standards (IEC 60502-1)

By choosing the PV AC/DC cable, you opt for a high-performance, reliable and durable solution, perfectly suited for demanding photovoltaic installations and outdoor environments.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Aluminum
Conductor shape
Round, stranded and compacted
Conductor flexibility
Class 2 acc. to IEC 60228
Insulation
Extruded XLPE compound
Insulation colour
Natural
Lay Up
Single core
Outer sheath
PVC compound
Sheath colour
Black

Dimensional characteristics

Dimensional characteristics

Number of cores
1
Conductor cross-section
240 mm²
Conductor diameter
18.5 mm
Average insulation thickness
2.0 mm
Diameter over insulation
22.8 mm
Nominal outer sheath thickness
1.8 mm
Nominal outer diameter
27.4 mm
Approximate weight
960 kg/km

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
1,5/1,5 (1,8) kV DC - 1,0/1,0 (1,2) kV AC
Max. DC resistance of the conductor at 20°C
0.125 Ohm/km
A.C. Conductor resist. 50Hz and at 90 °C
0.162 Ohm/km
Permissible short circuit current conductor 1s
22.7 kA

Resources

Resources

Declaration of Performance

  • Declaration of Performance n° : 1001392-ITBP
  • Certification Date : 7/1/26
  • AVCP (Assessment and Verification of Constancy of Performance) : System 3
  • Notified body : 0051
  • Declared performance : Eca

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close