Applications
These instrumentation and communication cable are used to transmit analogue or digital signals in measurement and process control .They are well adapted to underground use in industrial application where chemical and mechanical protections are needed (refinery areas, chemical plant…) .
Nexans code
- 1st serie = number of pairs, triples or quads: 01 to 27
- 2nd serie = pair (IP), triple (IT), quad (IQ)
- 3rd serie = conductor 05 (1 x 0.8 mm), 09 (7 x0.4 mm) or 15 (7 x 0.52 mm)
- 4th serie = overall screen (EG), individual screen + overall screen (EI)
- 5th serie = mechanical protection: without metal tape (SF), with steel tape (FA), with lead and steel tape (PF)
Design
Conductor:
Solid plain copper 0.50 mm² (1 x 0.80 mm) or stranded plain copper cross-section 0.88 mm² (7 x 0.40 mm) or 1.5 mm² (7 x 0.52 mm)
Insulation:
Polyvinyl chloride (PVC)
Overall screen:
Polyester tape
Tinned copper drain wire
Aluminium/polyester tape
Inner sheath:
Polyvinyl chloride (PVC)
Armour:
Double steel tape
Outer sheath:
Polyvinyl chloride (PVC)
Colour: light-blue or grey
Core identification
Pair: natural - red
Triple: natural - red - blue
Quad: natural - red - blue - yellow
Natural cores printed with pair/triple number
Marking
GORSE - Number of pair/triple/quad IP/IT/IQ 05/09/15 EG FA + metric marking
|