Single core MV HEPR insulated cable 8,7/15 kV

Send link to this page print Your Nexans contact on this page
Single core MV HEPR insulated cable 8,7/15 kV

Key element of the power distribution system to the end-users
Single core with copper or aluminium conductor 8,7/15 kV

MediaStripG7
Standards
International  IEC 60502-2
Description

Application

MV network is a key element of the power distribution system to the end-users; its performance and reliability are strictly related to the quality of cable and accessories.

 

In the medium voltage segment, HEPR insulation permits good cable performance at conductor's operating temperature as high as 90°C, with peaks of 130°C, insulation provides also good short circuit resistance up to 250°C and matches high current carrying capacity with good safety margins.MEDIASTRIPG7 is an easy stripping cable (the outer semiconductor can be removed at room temperature )

 

Construction

  • Conductor : copper or aluminium (stranded conductors flexibility class 2)
  • Insulation : HEPR G7
  • Screen : copper wires or tapes
  • Outer sheath : PVC

 

Upon request may provide cables fire retardant according to :

IEC 60332-3-22 (CAT A)
IEC 60332-3-23 (CAT B)
IEC 60332-3-24 (CAT C)


 TOP
Characteristics
Construction characteristics
Conductor material Copper or Aluminium  
Insulation HEPR(Cross-linked elastomeric)  
Screen Copper wires or tapes  
Outer sheath PVC  
Dimensional characteristics
Number of cores 1  
Electrical characteristics
Rated Voltage Uo/U (Um) 8.7/15 kV  
Usage characteristics
Bending factor when laying 14(xD)  
Flame retardant IEC 60332-1-2  
Max. conductor temperature in service 90°C  
Minimum installation temperature 0°C  

 TOP
HEPR MV singlecore 8,7-15kV unarmored

 

 

 

 

 

 

 

 

 

 

 

 

Nominal
cross 
section






mm²

Nominal 
diameter
of
conductor





mm

Insulation
thickness







mm

Oversheath
thickness







mm

Overall
diameter
approx






mm

Nominal
net weight
copper
cable


CU


kg/km

Nominal
net weight
aluminium
cable


AL


kg/km

Current
carryng
capacity
laid in
ground at
20°C
Rt:1 °Cm/WA
trefoil
CU

Current
carryng
capacity
laid in
air at
30 °C

trefoil
CU

Max ac 
resistance
of
conductor
at
90 °C

trefoil
CU
Ω/km

Phase
reactance

at 50 Hz



trefoil

Ω/km

Nominal
capacitance







μF/km

25

6.0

4.5

1.8

24.2

750

600

150

155

0.936

0.144

0.18

35

7.0

4.5

1.8

25.2

860

660

180

188

0.675

0.137

0.19

50

8.2

4.5

1.8

26.5

1010

720

213

225

0.499

0.130

0.21

70

9.9

4.5

1.8

28.2

1240

830

262

280

0.345

0.122

0.24

95

11.5

4.5

1.8

29.9

1520

960

314

345

0.249

0.116

0.26

120

13.1

4.5

1.9

31.8

1780

1070

356

398

0.197

0.112

0.29

150

14.3

4.5

1.9

33.1

2100

1210

398

450

0.162

0.109

0.31

185

16.1

4.5

2.0

35.2

2470

1360

453

517

0.129

0.106

0.33

240

18.5

4.5

2.1

37.9

3050

1590

525

613

0.100

0.101

0.37

300

20.7

4.5

2.1

40.2

3690

1830

590

705

0.080

0.098

0.41

400

23.5

4.5

2.2

43.4

4570

2190

669

815

0.064

0.095

0.45

500

26.5

4.5

2.3

46.7

5630

2590

760

945

0.052

0.091

0.50

630

30.0

4.5

2.4

50.6

7170

3270

850

1088

0.043

0.090

0.58