italiano Login Get Registered Catalog Browser Contact Us
Global expert in cables and cabling system

About Nexans

Products and Solutions

Customer Service

Work at Nexans

News and Press

Go

Three cores MV XLPE insulated cable 18/30 kV

Send link to this page print Your Nexans contact on this page
Three cores MV XLPE insulated cable 18/30 kV

Key element of the power distribution system to the end-users
Three cores with copper or aluminium conductor 18/30 kV

XPLE 4E
Standards
International  IEC 60502-2
Description

Application

 

MV network is a key element of the power distribution system to the end-users; its performance and reliability are strictly related to the quality of cable and accessories.

 

In the medium voltage segment, XLPE insulation permits good cable performance at conductor's operating temperature as high as 90°C, and matches high current carrying capacity with good safety margins.

 

Construction

  • Conductor : copper or aluminium 
  • Insulation : XLPE
  • Outer sheath : PVC 

 

Products that we can offer armoured or not armoured


 TOP
Characteristics
Construction characteristics
Conductor material Copper or Aluminium  
Insulation XLPE (Cross-linked Polyethylene)  
Outer sheath PVC  
Dimensional characteristics
Number of cores 3  
Electrical characteristics
Rated Voltage Uo/U (Um) 18/30 kV  

 TOP
MV XLPE insulated three cores unarmoured 18-30kV

 

 

 

 

 

 

 

 

 

 

 

 

Nominal
cross 
section






mm²

Nominal 
diameter
of
conductor





mm

Insulation
thickness







mm

Oversheath
thickness







mm

Overall
diameter
approx






mm

Nominal
net weight
copper
cable


CU


kg/km

Nominal
net weight
aluminium
cable


AL


kg/km

Current
carryng
capacity
laid in
ground at
20°C
Rt:1 °Cm/WA
trefoil
CU

Current
carryng
capacity
laid in
air at
30 °C

trefoil
CU

Max ac 
resistance
of
conductor
at
90 °C

trefoil

Ω/km

Phase
reactance

at 50 Hz



trefoil

Ω/km

Nominal
capacitance







μF/km

35

7.0

8.0

3.0

72.3

5400

5400

175

175

0.670

0.150

0.13

50

8.1

8.0

3.1

75.0

6000

5140

216

218

0.497

0.153

0.13

70

9.9

8.0

3.2

79.0

7100

5860

262

275

0.344

0.134

0.15

95

11.5

8.0

3.3

82.7

8300

6600

308

314

0.248

0.127

0.16

120

12.9

8.0

3.4

86.3

9400

7230

350

370

0.196

0.122

0.18

150

14.2

8.0

3.5

89.4

10500

7840

390

418

0.160

0.118

0.19

185

15.9

8.0

3.6

93.6

12100

8750

442

475

0.128

0.114

0.21

240

18.3

8.0

3.8

99.8

14400

10000

514

551

0.098

0.109

0.22

300

20.7

8.0

4.0

105.0

17000

11420

575

627

0.080

0.105

0.24

400

23.5

8.0

4.2

112.3

20400

13260

627

694

0.064

0.102

0.27


MV XLPE insulated three cores armoured 18-30kV

 

 

 

 

 

 

 

 

 

 

 

 

Nominal
cross 
section






mm²

Nominal 
diameter
of
conductor





mm

Insulation
thickness







mm

Oversheath
thickness







mm

Overall
diameter
approx






mm

Nominal
net weight
copper
cable


CU


kg/km

Nominal
net weight
aluminium
cable


AL


kg/km

Current
carryng
capacity
laid in
ground at
20°C
Rt:1 °Cm/WA
trefoil
CU

Current
carryng
capacity
laid in
air at
30 °C

trefoil
CU

Max ac 
resistance
of
conductor
at
90 °C

trefoil

Ω/km

Phase
reactance

at 50 Hz



trefoil

Ω/km

Nominal
capacitance







μF/km

35

7.0

8.0

3.2

82.2

9000

8380

175

171

0.670

0.165

0.13

50

8.1

8.0

3.4

86.8

10800

9940

216

214

0.497

0.157

0.13

70

9.9

8.0

3.5

91.0

12000

10870

262

261

0.344

0.147

0.15

95

11.5

8.0

3.6

95.2

13600

11900

303

313

0.248

0.139

0.16

120

12.9

8.0

3.7

98.8

14800

12630

345

361

0.196

0.134

0.18

150

14.2

8.0

3.8

102.0

16200

13540

386

408

0.160

0.129

0.19

185

15.9

8.0

4.0

108.2

19600

16250

432

466

0.128

0.125

0.21

240

18.3

8.0

4.2

113.4

22500

18100

454

541

0.098

0.120

0.22


 TOP