italiano Login Get Registered Catalog Browser Contact Us
Global expert in cables and cabling system

About Nexans

Products and Solutions

Customer Service

Work at Nexans

News and Press

Go

Three cores MV XLPE insulated cable 6/10 kV

Send link to this page print Your Nexans contact on this page
Three cores MV XLPE insulated cable 6/10 kV

Key element of the power distribution system to the end-users
Three cores with copper or aluminium conductor 6/10 kV

XPLE 4E
Standards
International  IEC 60502-2
Description

Application

 

MV network is a key element of the power distribution system to the end-users; its performance and reliability are strictly related to the quality of cable and accessories.

 

In the medium voltage segment, XLPE insulation permits good cable performance at conductor's operating temperature as high as 90°C, and matches high current carrying capacity with good safety margins.

 

Construction

  • Conductor : copper or aluminium 
  • Insulation : XLPE
  • Outer sheath : PVC 

 

Products that we can offer armoured or not armoured


 TOP
Characteristics
Construction characteristics
Conductor material Copper or Aluminium  
Insulation XLPE (Cross-linked Polyethylene)  
Outer sheath PVC  
Dimensional characteristics
Number of cores 3  
Electrical characteristics
Rated Voltage Uo/U (Um) 6/10 kV  

 TOP
XLPE MV three cores unarmoured 6-10kV

 

 

 

 

 

 

 

 

 

 

 

 

Nominal
cross 
section






mm²

Nominal 
diameter
of
conductor





mm

Insulation
thickness







mm

Oversheath
thickness







mm

Overall
diameter
approx






mm

Nominal
net weight
copper
cable


CU


kg/km

Nominal
net weight
aluminium
cable


AL


kg/km

Current
carryng
capacity
laid in
ground at
20°C
Rt:1 °Cm/WA
trefoil
CU

Current
carryng
capacity
laid in
air at
30 °C

trefoil
CU

Max ac 
resistance
of
conductor
at
90 °C

trefoil

Ω/km

Phase
reactance

at 50 Hz



trefoil

Ω/km

Nominal
capacitance







μF/km

25

6.0

3.4

2.2

45.8

2450

 

144

138

0.930

0.129

0.20

35

7.0

3.4

2.3

48.4

2890

2270

175

166

0.670

0.121

0.22

50

8.1

3.4

2.4

51.0

3390

2530

216

214

0.497

0.115

0.25

70

9.9

3.4

2.5

55.1

4250

3020

262

271

0.344

0.108

0.28

95

11.5

3.4

2.6

59.3

5300

3600

308

314

0.248

0.102

0.32

120

12.9

3.4

2.8

62.4

6250

4090

350

366

0.196

0.099

0.35

150

14.2

3.4

2.8

65.5

7280

4620

390

413

0.160

0.096

0.38

185

15.9

3.4

2.9

69.7

8650

5300

442

475

0.128

0.093

0.41

240

18.3

3.4

3.1

76.0

10800

6400

514

551

0.098

0.090

0.46

300

20.7

3.4

3.3

81.1

13100

7520

575

627

0.080

0.087

0.51

400

23.5

3.4

3.5

88.4

16100

8960

627

675

0.064

0.085

0.56


XLPE MV three cores armoured 6-10kV

 

 

 

 

 

 

 

 

 

 

 

 

Nominal
cross 
section






mm²

Nominal 
diameter
of
conductor





mm

Insulation
thickness







mm

Oversheath
thickness







mm

Overall
diameter
approx






mm

Nominal
net weight
copper
cable


CU


kg/km

Nominal
net weight
aluminium
cable


AL


kg/km

Current
carryng
capacity
laid in
ground at
20°C
Rt:1 °Cm/WA
trefoil
CU

Current
carryng
capacity
laid in
air at
30 °C

trefoil
CU

Max ac 
resistance
of
conductor
at
90 °C

trefoil

Ω/km

Phase
reactance

at 50 Hz



trefoil

Ω/km

Nominal
capacitance







μF/km

25

6.0

3.4

2.4

55.1

4690

 

144

138

0.930

0.142

0.20

35

7.0

3.4

2.5

57.8

5250

4630

175

166

0.670

0.133

0.22

50

8.1

3.4

2.6

60.3

5900

5040

216

209

0.497

0.126

0.25

70

9.9

3.4

2.7

64.5

7200

6060

263

256

0.344

0.119

0.28

95

11.5

3.4

2.9

69.2

8300

6600

309

313

0.248

0.112

0.32

120

12.9

3.4

3.0

72.3

9400

7230

350

356

0.196

0.109

0.35

150

14.2

3.4

3.1

75.4

10600

7930

389

408

0.160

0.106

0.38

185

15.9

3.4

3.2

79.6

12200

8850

442

466

0.128

0.102

0.41

240

18.3

3.4

3.4

86.8

15600

11200

504

541

0.098

0.099

0.46

300

20.7

3.4

3.6

93.1

18300

12720

555

618

0.080

0.096

0.51

400

23.5

3.4

3.8

100.5

21800

14660

606

665

0.064

0.093

0.56


 TOP