Single core MV XLPE insulated cable 6/10 kV

Send link to this page print Your Nexans contact on this page
Single core MV XLPE insulated cable 6/10 kV

Key element of the power distribution system to the end-users
Single core with copper or aluminium conductor 6/10 kV

XPLE 4E
Standards
International  IEC 60502-2
Description

Application

 

MV network is a key element of the power distribution system to the end-users; its performance and reliability are strictly related to the quality of cable and accessories.

 

In the medium voltage segment, XLPE insulation permits good cable performance at conductor's operating temperature as high as 90°C, and matches high current carrying capacity with good safety margins.

 

Construction

  • Conductor : copper or aluminium 
  • Insulation : XLPE
  • Outer sheath : PVC 

 

Products that we can offer armoured or not armoured


 TOP
Characteristics
Construction characteristics
Conductor material Copper or Aluminium  
Insulation XLPE (Cross-linked Polyethylene)  
Outer sheath PVC  
Dimensional characteristics
Number of cores 1  
Electrical characteristics
Rated Voltage Uo/U (Um) 6/10 kV  

 TOP
MV XLPE insulated single core unarmoured 6-10kV

 

 

 

 

 

 

 

 

 

 

 

 

Nominal
cross 
section






mm²

Nominal 
diameter
of
conductor





mm

Insulation
thickness







mm

Oversheath
thickness







mm

Overall
diameter
approx






mm

Nominal
net weight
copper
cable


CU


kg/km

Nominal
net weight
aluminium
cable


AL


kg/km

Current
carryng
capacity
laid in
ground at
20°C
Rt:1 °Cm/WA
trefoil
CU

Current
carryng
capacity
laid in
air at
30 °C

trefoil
CU

Max ac 
resistance
of
conductor
at
90 °C

trefoil

Ω/km

Phase
reactance

at 50 Hz



trefoil

Ω/km

Nominal
capacitance







μF/km

25

6.0

3.4

1.8

25.0

600

 

164

162

0.930

0.138

0.20

35

7.0

3.4

1.8

26.0

710

500

185

190

0.670

0.130

0.22

50

8.1

3.4

1.8

27.0

840

550

225

238

0.497

0.124

0.25

70

9.9

3.4

1.8

29.0

1100

690

277

295

0.344

0.117

0.28

95

11.5

3.4

1.8

30.5

1350

790

328

356

0.248

0.11

0.32

120

12.9

3.4

1.8

31.7

1600

880

370

408

0.196

0.107

0.35

150

14.2

3.4

1.8

33.3

1850

960

421

466

0.160

0.104

0.38

185

15.9

3.4

1.9

35.3

2250

1140

472

532

0.128

0.1

0.41

240

18.3

3.4

2

38.0

2800

1340

544

627

0.098

0.097

0.46

300

20.7

3.4

2.1

41.1

3450

1600

616

722

0.080

0.094

0.51

400

23.5

3.4

2.2

44.2

4300

1920

699

836

0.064

0.091

0.56

500

26.5

3.4

2.2

47.3

5300

2270

782

950

0.051

0.088

0.61

630

30.1

3.4

2.4

51.0

6700

2810

876

1083

0.042

0.086

0.68


MV XLPE insulated single core armoured 6-10kV

 

 

 

 

 

 

 

 

 

 

 

 

Nominal
cross 
section






mm²

Nominal 
diameter
of
conductor





mm

Insulation
thickness







mm

Oversheath
thickness







mm

Overall
diameter
approx






mm

Nominal
net weight
copper
cable


CU


kg/km

Nominal
net weight
aluminium
cable


AL


kg/km

Current
carryng
capacity
laid in
ground at
20°C
Rt:1 °Cm/WA
trefoil
CU

Current
carryng
capacity
laid in
air at
30 °C

trefoil
CU

Max ac 
resistance
of
conductor
at
90 °C

trefoil

Ω/km

Phase
reactance

at 50 Hz



trefoil

Ω/km

Nominal
capacitance







μF/km

25

6.0

3.4

1.8

31.1

970

 

164

162

0.930

0.154

0.20

35

7.0

3.4

1.8

31.2

1100

890

185

190

0.670

0.149

0.22

50

8.1

3.4

1.8

33.8

1250

960

225

238

0.497

0.138

0.25

70

9.9

3.4

1.9

35.3

1500

1090

277

295

0.344

0.130

0.28

95

11.5

3.4

1.9

37.0

1790

1220

329

356

0.248

0.123

0.32

120

12.9

3.4

2

39.5

2150

1430

371

408

0.196

0.118

0.35

150

14.2

3.4

2

40.0

2430

1540

422

466

0.160

0.117

0.38

185

15.9

3.4

2.1

43.2

2880

1760

468

522

0.128

0.112

0.41

240

18.3

3.4

2.2

45.2

3550

2080

534

618

0.098

0.109

0.46

300

20.7

3.4

2.3

48.4

4200

2340

596

703

0.080

0.105

0.51

400

23.5

3.4

2.4

52.5

5250

2870

668

798

0.064

0.101

0.56

500

26.5

3.4

2.5

56.2

6400

3360

729

884

0.051

0.100

0.61

630

30.1

3.4

2.6

60.3

7800

3910

781

988

0.042

0.100

0.68


 TOP