AFNOR NF M 87-202 IOS Unarmoured

Send link to this page print Your Nexans contact on this page
AFNOR NF M 87-202 IOS Unarmoured - Instrumentation cables 250 V
- Individual & Overall Screen (IOS)
- Hydrocarbons resistant
Standards
International  IEC 60332-1-2
Description

Applications

These instrumentation and communication cable are used to transmit analogue or digital signals in measurement and process control where hydrocarbons may be present. The individual screening of each pair limits the consequence of crosstalk.

 

Nexans code

  • 1st serie = number of pairs, triples or quads: 01 to 27
  • 2nd serie = pair (IP), triple (IT), quad (IQ)
  • 3rd serie = conductor 05 (1 x 0.8 mm), 09 (7 x 0.4 mm) or 15 (7 x 0.52 mm)
  • 4th serie = collective screen (EG), individual screen + collective screen (EI)
  • 5th serie = mechanical protection: without metal tape (SF), with steel tape (FA), with lead and steel tape (PF)

Design

Conductor

Solid plain copper 0.50 mm² (1 x 0.80 mm) or stranded plain copper cross-section 0.88 mm² (7 x 0.40 mm) 

Insulation:

Polyvinyl chloride (PVC)

Individual screen:

Polyester tape

Tinned copper drain wire

Aluminium/polyester tape

Individual sheath:

Polyvinyl chloride (PVC)

Collective screen:

Polyester tape

Tinned copper drain wire

Aluminium/polyester tape

Outer sheath:

Polyvinyl chloride (PVC)

Colour: light-blue or grey

 

Core identification

Pair: natural - red
Triple: natural - red - blue
Blue individual sheath printed with pair or triple number
 

 

Marking

GORSE - Number of pair/triple IP/IT  05/09 EI SF + metric marking


 TOP
Characteristics
Construction characteristics
Conductor material Plain copper  
Insulation PVC  
Individual screen Tinned copper drain wire + aluminium/polyester tape  
Individual sheath PVC  
Overall screen Tinned copper drain wire + aluminium/polyester tape  
Outer sheath PVC  
Sheath colour Light blue  
Electrical characteristics
Operating voltage 250V  
Usage characteristics
Flame retardant NFC 32070 C2, IEC 60332-1-2  
Chemical resistance Hydrocarbons resistant  
Electro magnetic interference resistance Yes  
Operating temperature, range -20 .. 60°C  
Max. conductor temperature in service 70°C  
Standard NFM  

 TOP
Results   14/14
Select all Items Nexans ref. Name Cross section (mm²) nb pairs nb triples
10048421 03 IP 05 EI SF 0.5 3 0
10048584 03 IP 09 EI SF 0.88 3 0
10048422 07 IP 05 EI SF 0.5 7 0
10048550 07 IP 09 EI SF 0.88 7 0
10048426 07 IT 05 EI SF 0.5 0 7
10048541 07 IT 09 EI SF 0.88 0 7
10048423 12 IP 05 EI SF 0.5 12 0
10048555 12 IP 09 EI SF 0.88 12 0
10048427 12 IT 05 EI SF 0.5 0 12
10048548 12 IT 09 EI SF 0.88 0 12
10048424 19 IP 05 EI SF 0.5 19 0
10048565 19 IP 09 EI SF 0.88 19 0
Make to order product 10048425 27 IP 05 EI SF 0.5 27 0
10048585 27 IP 09 EI SF 0.88 27 0
Add to favorites

 TOP
Electrical Data NF M 87202


 TOP
Selling delivery information

Minimum bending radius:

1 core: 10 x outer diameter
To be doubled during laying operations


Nexans © copyright 2001 - 2012   Legal Notice | Contact Us | Site Map